Industrial Liquid Level Measurement & Control Application Notes


If you would like would like one of our technical specialists to evaluate your application and provide a recommended equipment quotation then please contact us with a completed Applications Data Sheet. AMI routinely provides dimensioned sensor drawings for customer approval to ensure there are no surprises or interference issues.

The following brief applications information is provided. This is only a partial list of applications for which AMI can provide measurement solutions.

Applications Considerations

The most effective application of capacitance to measure levels are when the dielectric value of the media remains constant over the operating range of interest. If the transmitter is calibrated to this condition and it remains constant then the level reading will remain accurate. Several factors have the ability to introduce an error into the level reading by shifting the environment away from the calibrated condition.

Composition Changes - Most materials have differing dielectric values. If the composition of a mixture changes significantly over time then this may cause an inaccurate level measurement due to the shift in dielectric value. Low dielectric value materials (non-conductive) are most susceptible to this affect. Mixtures with high dielectric values (conductive materials) are much less affected by this change. Impurities to an otherwise constant composition material will have varying degrees of affect depending on their relative dielectric value difference from the bulk material.

Density Changes - In most plant operations the dielectric value of a material is not a monitored or considered an important parameter. A simple way to decide if changing dielectric values may be a problem is to determine if the density of the material is changing. There is typically a direct correlation between the density of a material and the dielectric value. One obvious parameter that can cause this change is variations in temperature another is composition. If your applications density in shifting by some % then you can expect a similar error in the level reading as referenced to the calibrated condition. If the density (inferred dielectric) is higher than the calibrated condition by 10% then your level reading will be 10% higher than the actual level. The opposite is true in reverse.

Moisture - Water is very conductive and has a high dielectric value. If the bulk material being measured is normally non-conductive but can contain some moisture then any change in the moisture content will affect the level reading. In a constant level condition, as the moisture increases the level reading will read false on the high side. This is a common problem if a hydrocarbon tank collects enough water in the bottom to eventually touch the bottom of the capacitance probe - at this point it will likely jump to a 100% reading. Other hygroscopic materials (i.e. those that absorb moisture from the air) like powders or granular solids (such as polymer pellets) can also be susceptible to this effect.

The other common moisture related issue occurs when water enters the probe cover or transmitter housing through the installed plant conduit. This will cause the circuit to read a false high level and remain at 100%. The culprit is normally found to be a poorly sealed junction point or cover in the conduit. One very quick and simple solution to this problem is to backfill the nipple section directly on top of the probe with a common silicon RTV caulk. This area must of course be dried thoroughly before doing so. This will effectively create a barrier and prevent water from shorting out the sensors' signal to the transmitter. This problem can be avoided in many cases if the conduit routing is such that the transmitter housing is not at a low point in the wiring system.

Coating or Material Build Up - In some processes material adheres to the capacitance probe and/or tank wall forming a coating over time. Normally this reaches some equilibrium state where the coating layer thickness remains basically constant. In these cases it is best to delay calibration of the transmitter until the level probe is fully coated. If this is not done then a false high reading will be seen periodically as the coating builds up and recalibration will be required each time to bring the instrument back into operation. Plant personnel and I&E technicians should also be aware that the level reading will conversely read low after a coating process is cleaned and put back into operation. If possible it is best not to recalibrate and simply wait for the coating to re-develop.

The adverse affects of coating are much more pronounced and difficult to deal with when the material is conductive or water based. An example of a compounded problem would be where a thick, moist conductive coating formed on the probe, a new calibration was done and the coating on the exposed probe dried out (became much less conductive). In this case the probe would give a false low level signal. Such cases are difficult to address and capacitance may not be the optimum technique to use. Systems where a periodic cleaning cycle occurs can often keep buildup within acceptable levels. Operators will often recognize the gradual creep of the signal due to coating.

Tank Agitation - In tanks with agitation it is obviously important to locate the probe away from moving blades to avoid damage to the probe or internal tank components. Agitation may produce a vortex which can raise the liquid level on the probe. This will be seen as an increase in the level reading. Liquid splashing may also occur and been seen as increased and/or erratic level readings. The use of a stilling well probe or electronic damping can minimize these effects.

 

Specific Applications

On vehicle systems the transmitter and a dash mounted level readout are both powered from the vehicles 12VDC circuit. The rugged NEMA enclosure is well suited for direct mounting on the trailer tank either on top or remote mounting on the side for easier access.

 

Back to Liquid Level Instrumentation page

AMI Home Page | Sales | Industrial Level Sensors.html | Industrial Level Transmitters
Technical Support | Customer Service | E-Mail AMI